Stycznik pomocniczy DC; 4Z DILER-40-G(24VDC)
- Dodaj recenzję:
- Kod: 010223
-
Dostępność:
Brak
(0 szt.)
- szt.
- Cena brutto: 430,25 zł 349,80 zł
Stycznik pomocniczy DC; 4Z DILER-40-G(24VDC)
Program
Approbationen
|
General | |||
Standards
|
IEC/EN 60947, VDE 0660, UL, CSA | ||
Lifespan, mechanical
|
|||
AC operated
|
Operations | x 106 | 10 |
DC operated
|
Operations | x 106 | 20 |
Maximum operating frequency
|
Ops./h | ||
Maximum operating frequency
|
Operations/h | 9000 | |
Climatic proofing
|
Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 |
||
Climatic proofing
|
Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30 | ||
Ambient temperature
|
°C | ||
Open
|
°C | -25- 50 | |
Enclosed
|
°C | -25- 40 | |
Mounting position
|
|||
Mounting position
|
As required, except vertical with terminals A1/A2 at the bottom | ||
Mechanical shock resistance (IEC/EN 60068-2-27)
|
|||
Half-sinusoidal shock, 10 ms
|
|||
Basic unit with auxiliary contact module
|
g | ||
N/O contact
|
g | 10 | |
N/C contact
|
g | 8 | |
Protection type
|
IP20 | ||
Protection against direct contact when actuated from front (EN 90274)
|
Finger and back-of-hand proof | ||
Weight
|
|||
AC operated
|
kg | 0.17 | |
DC operated
|
kg | 0.2 | |
Terminal capacities
|
mm2 | ||
Screw terminals
|
|||
Solid
|
mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
|
Flexible with ferrule
|
mm2 | 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) |
|
Solid or stranded
|
AWG | 18 - 14 | |
Terminal screw
|
M3.5 | ||
Pozidriv screwdriver
|
Size | 2 | |
Standard screwdriver
|
mm | 0.8 x 5.5 1 x 6 |
|
Max. tightening torque
|
Nm | 1.2 | |
Spring-loaded terminals
|
|||
Solid
|
mm2 | 1 x (1 - 2.5) 2 x (1 - 2.5) |
|
Flexible with or without ferrule DIN 46228
|
mm2 | 1 x (1 - 2.5) 2 x (1 - 2.5) |
|
Solid or stranded
|
AWG | 1 x (16 - 14) 2 x (16 - 14) |
|
Standard screwdriver
|
mm | 0.6 x 3.5 | |
Contacts | |||
Positive operating contacts to ZH 1/457, including auxiliary contact module
|
Yes | ||
Rated impulse withstand voltage
|
Uimp | V AC | 6000 |
Overvoltage category/pollution degree
|
III/3 | ||
Rated insulation voltage
|
Ui | V AC | 690 |
Rated operational voltage
|
Ue | V AC | 600 |
Safe isolation to VDE 0106 Part 101 and Part 101/A1
|
|||
between coil and auxiliary contacts
|
V AC | 300 | |
between the auxiliary contacts
|
V AC | 300 | |
Rated operational current
|
Ie | A | |
AC-15
|
|||
220/240 V
|
Ie | A | 6 |
380/415 V
|
Ie | A | 3 |
500 V
|
Ie | A | 1.5 |
DC-13
|
|||
DC-13 L/R - 15 ms
|
|||
Contacts in series:
|
A | ||
1
|
24 V | A | 2.5 |
2
|
60 V | A | 2.5 |
3
|
110 V | A | 1.5 |
3
|
220 V | A | 0.5 |
Control circuit reliability (at Ue= 24 V DC, Umin= 17 V, I min= 5.4 mA)
|
Failure rate | λ | <10-8, < one failure at 100 million operations |
Conv. thermal current
|
Ith | A | 10 |
Short-circuit rating without welding
|
|||
Maximum overcurrent protective device
|
|||
220/240 V
|
PKZM0 | 4 | |
380/415 V
|
PKZM0 | 4 | |
Short-circuit protection maximum fuse
|
|||
500 V
|
A gG/gL | 6 | |
500 V
|
A fast | 10 | |
Current heat loss at Ith
|
|||
AC operated
|
W | 0.2 | |
DC operated
|
W | 0.3 | |
Magnet systems | |||
Voltage tolerance
|
x Uc | ||
AC operated
|
x Uc | ||
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz
|
Pick-up | x Uc | 0.8- 1.1 |
Dual-frequency coil 50/60 Hz
|
Pick-up | x Uc | 0.85- 1.1 |
DC operated
|
x Uc | ||
Pick-up voltage
|
Pick-up | x Uc | 0.85- 1.3 |
at 24 V: without auxiliary contact component (40 °C)
|
Pick-up | x Uc | 0.7- 1.3 |
Power consumption
|
|||
50 Hz
|
Pick-up | VA | 25 |
50 Hz
|
Sealing | VA | 4.6 |
50 Hz
|
Sealing | W | 1.3 |
60 Hz
|
Pick-up | VA | 25 |
60 Hz
|
Sealing | VA | 4.6 |
60 Hz
|
Sealing | W | 1.3 |
50/60 Hz
|
Pick-up | VA | 30 29 |
50/60 Hz
|
Sealing | VA | 5.4 3.9 |
50/60 Hz
|
Sealing | W | 1.6 1.1 |
DC operated
|
Pull-in = sealing | W | 2.6 |
Duty factor
|
% DF | 100 | |
Switching times at 100 % Uc(approximate values)
|
|||
AC operated closing delay
|
ms | 14- 21 | |
AC operated N/O contact opening delay
|
ms | 8- 18 | |
AC operated With auxiliary contact module Max. closing delay
|
ms | 45 | |
DC operated closing delay
|
ms | 26- 35 | |
DC operated N/O contact opening delay
|
ms | 15- 25 | |
DC operated With auxiliary contact module Max. closing delay
|
ms | 70 | |
Notes | |||
Notes Making and breaking conditions to DC-13, time constant as stated See transparent overlay "Fuses" for time/current characteristics (please enquire) Use only equal cross-sections |
Technical data according to ETIM 4.0
Connection type main circuit
|
Screw connection | ||
Rated control voltage Us at DC
|
V | 24 | |
Rated control voltage Us at AC 60HZ
|
V | 0 | |
Rated control voltage Us at AC 50HZ
|
V | 0 | |
Number of auxiliary contacts as changeover contacts
|
0 | ||
Rated operation current Ie , 400 V
|
A | 3 | |
Number of auxiliary contacts as N/Cs
|
0 | ||
Number of auxiliary contacts as N/Os
|
4 | ||
Voltage type for actuation
|
DC | ||
Number of auxiliary contacts as N/Os, leading
|
0 | ||
Number of auxiliary contacts as N/Cs, delayed switching
|
0 |
CAD-Data
|