Stycznik mocy I=25A [AC-3] 1Z 0R

  • szt.
  • Rabat: -262,16 zł (40 %)
  • (Rabat brutto: -322,46 zł (40 %))
  • Cena brutto: 483,68 zł / szt. 393,24 zł / szt.

Stycznik mocy, I=25A [AC-3] DILM25-32(230V50HZ,240V60HZ)

Program
Product range
    Contactors
Application
    Contactors for Motors
Subrange
    Complete devices up to 170 A
Connection technique
    Screw terminals
Rated operational current
     
AC-3
     
380 V 400 V
Ie A 25
AC-1
     
Conventional free air thermal current, 3 pole, 50 - 60 Hz
     
Open
     
at 60 °C
Ith =Ie A 40
Max. rating for three-phase motors, 50 - 60 Hz
     
AC-3
     
220 V 230 V
P kW 7.5
380 V 400 V
P kW 11
660 V 690 V
P kW 14
AC-4
     
220 V 230 V
P kW 3.5
380 V 400 V
P kW 6
660 V 690 V
P kW 8.5
Contacts
     
Auxiliary contacts: = safety function, by positive opening to IEC/EN 60947-5-1
     
N/O = Normally open
    3 N/O
N/C = Normally closed
    2 N/C
Instructions
    Contacts to EN 50 012.
with mirror contact.
Contact sequence
   
Voltage AC/DC
    AC operation
Approbationen
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29096
UL CCN NLDX
CSA File No. 012528
CSA Class No. 2411-03, 3211-04
NA Certification UL Listed, CSA certified
Specially designed for NA No
 
General
Standards
    IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
     
AC operated
Operations x 106 10
DC operated
Operations x 106 10
Operating frequency, mechanical
     
AC operated
Operations/h   5000
DC operated
Operations/h   5000
Climatic proofing
    Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature
  °C  
Open
  °C -25- 60
Enclosed
  °C -25- 40
Storage
  °C -40- 80
Mounting position, AC- and DC operated
   
Mechanical shock resistance (IEC/EN 60068-2-27)
     
Half-sinusoidal shock, 10 ms
     
Main contacts
     
N/O contact
  g 10
Auxiliary contacts
     
N/O contact
  g 7
N/C contact
  g 5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
     
Half-sinusoidal shock, 10 ms
     
Main contacts
     
N/O contact
  g 6.9
Auxiliary contacts
     
N/O contact
  g 5.3
N/C contact
  g 3.5
Protection type
    IP00
Protection against direct contact when actuated from front (EN 90274)
    Finger- and back-of-hand proof
Weight
     
AC operated
  kg 0.42
DC operated
  kg 0.48
Terminal capacity main cable
     
Solid
  mm2 1 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule
  mm2 1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded
  mm2 1 x 16
Solid or stranded
  AWG 18 - 6
Main cable connection screw/bolt
    M5
Tightening torque
  Nm 3.2
Terminal capacity control circuit cables
     
Solid
  mm2 1 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule
  mm2 1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
  AWG 18 - 14
Control circuit cable connection screw/bolt
    M3.5
Tightening torque
  Nm 1.2
Tool
     
Main cable
     
Pozidriv screwdriver
  Size 2
Standard screwdriver
  mm 0.8 x 5.5
1 x 6
Control circuit cables
     
Pozidriv screwdriver
  Size 2
Standard screwdriver
  mm 0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
     
Solid
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
  mm2 1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
  AWG 18 - 14
Tool
     
Stripping length
  mm 10
Screwdriver blade width
  mm 3.5
Main conducting paths
Rated impulse withstand voltage
Uimp V AC 8000
Overvoltage category/pollution degree
    III/3
Rated insulation voltage
Ui V AC 690
Rated operational voltage
Ue V AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
     
between coil and contacts
  V AC 440
between the contacts
  V AC 440
Making capacity (p.f. to IEC/EN 60947)
     
 
Up to 690 V A 350
Breaking capacity
     
220/230 V
  A 250
380/400 V
  A 250
500 V
  A 250
660/690 V
  A 150
Short-circuit rating
     
Short-circuit protection maximum fuse
     
Type “2” coordination
     
400 V
gG/gL 500 V A 35
690 V
gG/gL 690 V A 35
Type “1” coordination
     
400 V
gG/gL 500 V A 100
690 V
gG/gL 690 V A 50
AC
AC-1 duty
     
Conventional free air thermal current, 3 pole, 50 - 60 Hz
     
Open
     
at 40 °C
Ith =Ie A 45
at 50 °C
Ith =Ie A 43
at 55 °C
Ith =Ie A 42
at 60 °C
Ith =Ie A 40
enclosed
Ith A 36
Conventional free air thermal current, 1 pole
     
open
Ith A 100
enclosed
Ith A 90
AC-3 duty
     
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole
Ie    
220/230 V
Ie A 25
240 V
Ie A 25
380/400 V
Ie A 25
415 V
Ie A 25
440V
Ie A 25
500 V
Ie A 25
660/690 V
Ie A 15
Motor rating
P kWh  
220/230 V
P kW 7.5
240V
P kW 8.5
380/400 V
P kW 11
415 V
P kW 14.5
440 V
P kW 15.5
500 V
P kW 17.5
660/690 V
P kW 14
AC-4 duty
     
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole
Ie    
220/230 V
Ie A 13
240 V
Ie A 13
380/400 V
Ie A 13
415 V
Ie A 13
440 V
Ie A 13
500 V
Ie A 13
660/690 V
Ie A 10
Motor rating
P kWh  
220/230 V
P kW 3.5
240 V
P kW 4
380/400 V
P kW 6
415 V
P kW 6.5
440 V
P kW 7
500 V
P kW 8
660/690 V
P kW 8.5
DC
Rated operational current, open
     
DC-1 operation
     
60 V
Ie A 40
110 V
Ie A 40
220 V
Ie A 40
440 V
Ie A 2.9
DC-3 operation
     
60 V
Ie A 35
110 V
Ie A 35
220 V
Ie A 10
440 V
Ie A 0.6
DC-5 operation
     
60 V
Ie A 35
110 V
Ie A 35
220 V
Ie A 10
440 V
Ie A 0.6
Current heat loss (3 pole)
Current heat loss at Ith
  W 9.6
Current heat loss at Ieto AC-3/400 V
  W 3.8
Impedance per pole
  mΩ 2
Magnet systems
Voltage tolerance
  x Uc  
AC operated
Pick-up x Uc 0.8- 1.1
Drop-out voltage AC operated
Drop-out x Uc 0.3- 0.6
DC operated
Pick-up x Uc 0.7- 1.2
Notes
    at least smoothed two-phase bridge rectifier or three-phase rectifier
DC operated
Drop-out x Uc 0.15- 0.6
Power consumption of the coil in a cold state and 1.0 x Uc
     
50 Hz
Pick-up VA 52
50 Hz
Sealing VA 7.1
50 Hz
Sealing W 2.1
60 Hz
Pick-up VA 67
60 Hz
Sealing VA 8.7
60 Hz
Sealing W 2.6
50/60 Hz
Pick-up VA 62
58
50/60 Hz
Sealing VA 9.1
6.5
50/60 Hz
Sealing W 2.5
2
DC operated
Pick-up W 12
DC operated
Sealing W 0.5
Duty factor
  % DF 100
Switching times at 100 % Uc(approximate values)
     
Main contacts
     
AC operated
     
Closing delay
  ms 16- 22
Opening delay
  ms 8- 14
DC operated
  ms  
Closing delay
  ms 47
Opening delay
  ms 30
Arcing time
  ms 10
Lifespan, mechanical; Coil 50/60 Hz
at 50 Hz   Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general”
Electromagnetic compatibility (EMC)
Emitted interference
    to EN 60947-1
Interference immunity
    to EN 60947-1
Technical data according to ETIM 4.0
Number of main contacts as N/Os
    3
Rated operation current Ie at AC-1, 400 V
    45
Connection type main circuit
    Screw connection
Rated control voltage Us at AC 60HZ
  V 240
Number of auxiliary contacts as N/Os
    3
Rated control voltage Us at AC 50HZ
  V 230
Number of auxiliary contacts as N/Cs
    2
Suitable for rail-mounting
    No
Rated control voltage Us at DC
  V 0
Voltage type for actuation
    AC
Rated operation current Ie at AC-3, 400 V
  A 25
Number of N/Cs as main contact
    0
Motor rating at AC-3, 400 V
  kWh 11
Characteristics
1: Overload relay
2: Suppressor
Projektieren
Squirrel-cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 1 x rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket-elevators
Air conditioning system
General drives in manufacturing and processing machines
Extreme switching duty
Squirrel-cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 6 x rated motor current
Utilization category
100 % AC-4
Typical applications
Printing presses
Wire-drawing machines
Centrifuges
Special drives for manufacturing and processing machines
Dimensions
Contactor with auxiliary contact module
Lateral clearance to earthed parts: 6 mm

Opis pochodzi ze strony www.moeller.net .