Standards | | | IEC/EN 60947, VDE 0660, UL, CSA |
Lifespan, mechanical | | | |
AC operated | Operations | x 106 | 10 |
DC operated | Operations | x 106 | 10 |
Operating frequency, mechanical | | | |
AC operated | Operations/h | | 5000 |
DC operated | Operations/h | | 5000 |
Climatic proofing | | | Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 |
Ambient temperature | | °C | |
Open | | °C | -25- 60 |
Enclosed | | °C | -25- 40 |
Storage | | °C | -40- 80 |
Mounting position, AC- and DC operated | | | |
Mechanical shock resistance (IEC/EN 60068-2-27) | | | |
Half-sinusoidal shock, 10 ms | | | |
Main contacts | | | |
N/O contact | | g | 10 |
Auxiliary contacts | | | |
N/O contact | | g | 7 |
N/C contact | | g | 5 |
Protection type | | | IP00 |
Protection against direct contact when actuated from front (EN 90274) | | | Finger- and back-of-hand proof |
Terminal capacity main cable | | | |
Solid | | mm2 | 1 x (0.75 - 4) 2 x (0.75 - 2.5) |
Flexible with ferrule | | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
Solid or stranded | | AWG | 18 - 14 |
Terminal capacity control circuit cables | | | |
Solid | | mm2 | 1 x (0.75 - 4) 2 x (0.75 - 2.5) |
Flexible with ferrule | | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
Solid or stranded | | AWG | 18 - 14 |
Main cable connection screw/bolt | | | M3.5 |
Tightening torque | | Nm | 1.2 |
Control circuit cable connection screw/bolt | | | M3.5 |
Tightening torque | | Nm | 1.2 |
Tool | | | |
Main cable | | | |
Pozidriv screwdriver | | Size | 2 |
Standard screwdriver | | mm | 0.8 x 5.5 1 x 6 |
Control circuit cables | | | |
Pozidriv screwdriver | | Size | 2 |
Standard screwdriver | | mm | 0.8 x 5.5 1 x 6 |
|
Rated impulse withstand voltage | Uimp | V AC | 8000 |
Overvoltage category/pollution degree | | | III/3 |
Rated insulation voltage | Ui | V AC | 690 |
Rated operational voltage | Ue | V AC | 690 |
Safe isolation to VDE 0106 Part 101 and Part 101/A1 | | | |
between coil and contacts | | V AC | 400 |
between the contacts | | V AC | 400 |
Making capacity (p.f. to IEC/EN 60947) | | | |
| Up to 690 V | A | 144 |
Breaking capacity | | | |
220/230 V | | A | 120 |
380/400 V | | A | 120 |
500 V | | A | 100 |
660/690 V | | A | 70 |
Short-circuit rating | | | |
Short-circuit protection maximum fuse | | | |
Type “2” coordination | | | |
400 V | gG/gL 500 V | A | 20 |
690 V | gG/gL 690 V | A | 20 |
Type “1” coordination | | | |
400 V | gG/gL 500 V | A | 35 |
690 V | gG/gL 690 V | A | 25 |
|
AC-1 duty | | | |
Rated operational current | | | |
Conventional free air thermal current, 3 pole, 50 - 60 Hz | | | |
Open | | | |
at 40 °C | Ith =Ie | A | 22 |
at 50 °C | Ith =Ie | A | 21 |
at 60 °C | Ith =Ie | A | 20 |
enclosed | Ith | A | 18 |
Conventional free air thermal current, 1 pole | | | |
open | Ith | A | 60 |
enclosed | Ith | A | 54 |
Motor rating | P | kWh | |
Motor rating AC-1 230 V | | kW | 8 |
Motor rating AC-1 240 V | | kW | 9 |
Motor rating AC-1 380/400 V | | kW | 14 |
Motor rating AC-1 415 V | | kW | 15 |
Motor rating AC-1 440 V | | kW | 16 |
Motor rating AC-1 500 V | | kW | 18 |
Motor rating AC-1 690 V | | kW | 24 |
AC-3 duty | | | |
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole | Ie | | |
220/230 V | Ie | A | 12 |
240 V | Ie | A | 12 |
380/400 V | Ie | A | 12 |
415 V | Ie | A | 12 |
440V | Ie | A | 12 |
500 V | Ie | A | 10 |
660/690 V | Ie | A | 7 |
Motor rating | P | kWh | |
220/230 V | P | kW | 3.5 |
240V | P | kW | 4 |
380/400 V | P | kW | 5.5 |
415 V | P | kW | 7 |
440 V | P | kW | 7.5 |
500 V | P | kW | 7 |
660/690 V | P | kW | 6.5 |
|
Rated operational current, open | | | |
DC-1 operation | | | |
60 V | Ie | A | 22 |
110 V | Ie | A | 22 |
220 V | Ie | A | 6 |
440 V | Ie | A | 1.3 |
DC-3 operation | | | |
60 V | Ie | A | 20 |
110 V | Ie | A | 20 |
220 V | Ie | A | 1.5 |
440 V | Ie | A | 0.2 |
DC-5 operation | | | |
60 V | Ie | A | 20 |
110 V | Ie | A | 20 |
220 V | Ie | A | 1.5 |
440 V | Ie | A | 0.2 |
|
Current heat loss at Ith | | W | 4.7 |
Impedance per pole | | mΩ | 2.5 |
|
Voltage tolerance | | x Uc | |
AC operated 50 Hz | Pick-up | x Uc | 0.8- 1.1 |
AC operated 50/60 Hz | | x Uc | 0.8- 1.1 |
Drop-out voltage AC operated | Drop-out | x Uc | 0.3- 0.6 |
DC operated | Pick-up | x Uc | 0.7- 1.2 |
DC operated | Drop-out | x Uc | 0.15- 0.6 |
Power consumption of the coil in a cold state and 1.0 x Uc | | | |
AC operated 50/60 Hz | Pick-up | VA | 24 |
AC operated 50/60 Hz | Pick-up | W | 19 |
AC operated 50/60 Hz | Sealing | VA | 4 |
AC operated 50/60 Hz | Sealing | W | 1.2 |
DC operated | Pick-up | W | 4,5 |
DC operated | Sealing | W | 4,5 |
Duty factor | | % DF | 100 |
Switching times at 100 % Uc(approximate values) | | | |
Main contacts | | | |
AC operated | | | |
Closing delay | | ms | 15- 21 |
Opening delay | | ms | 9- 18 |
DC operated | | ms | |
Closing delay | | ms | 31 |
Opening delay | | ms | 12 |
Arcing time | | ms | 10 |
Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal). | | mA | 1 |
|
At least double-pulse bridge rectifier |