Kategorie

Przekaźnik progr. easy 24VDC, 8we, 4 wy EASY512-DC-RC

  • Kod: 274109
  • W magazynie: 1 szt.
  • (Gdańsk: 1.00)
  • Producent: EATON Electric
  • Cena netto: 529,14 zł881,90 zł
  • (Cena brutto: 650,84 zł)
  • szt.
  • Poleć produkt
Program
Product range
  Control relays easyRelay
Basic function
  easy500
 
  Stand alone
Inputs
   
Digital input count
  digital: 8
digital: 8; of which can be used as analog: 2
Digital
  8
of which can be used as analog
  2
Outputs
   
Type
  Relay
Quantity of outputs
  Relays: 4
Additional features
   
Display
  with display, with keypad
Real time clock
  
Software
  easySoft Basic/Pro
Supply voltage
  24 V DC
Software
  easySoft Basic/Pro
Approbationen
Product StandardsIEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-M1987; CE marking
UL File No.E135462
UL CCNNRAQ
CSA File No.012528
CSA Class No.2252-01 + 2258-02
NA CertificationUL Listed, CSA certified
Degree of ProtectionIEC: IP20, UL/CSA Type: -
 
General
Standards
  EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Mounting
  Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Terminal capacities
Solid
 mm20.2/4 (AWG 22 - 12)
Flexible with ferrule
 mm20.2/2.5 (AWG 22 - 12)
Standard screwdriver
 mm3.5 x 0.8
Max. tightening torque
 Nm0.6
Climatic environmental conditions
Operating ambient temperature
 °C-25 … 55, low temperatures to IEC 60068-2-1, high temperatures to IEC 60068-2-2
Condensation
  Take appropriate measures to prevent condensation
LCD display (clearly legible)
 °C0- 55
Storage
 °C-40- 70
Relative humidity, non-condensing (IEC/EN 60068-2-30)
 %5- 95
Air pressure (operation)
 hPa795- 1080
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
  IP20
Vibrations (IEC/EN 60068-2-6)
 Hz 
Constant amplitude 0.15 mm
 Hz10- 57
Constant acceleration 2 g
 Hz57- 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
 Impacts18
Drop to IEC/EN 60068-2-31
Drop heightmm50
Free fall, packaged (IEC/EN 60068-2-32)
 m1
Mounting position
  Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
  II/2
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
 kV 
Air discharge
 kV8
Contact discharge
 kV6
Electromagnetic fields (RFI), to IEC EN 61000-4-2
 V/m10
Radio interference suppression
  EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)
   
Supply cables
 kV2
Signal lines
 kV2
power pulses (surge) (IEC/EN 61000-4-5, level 2)
 kV0.5 (supply cables, symmetrical, EASY…DC)
Radiated RFI (IEC/EN 61000-4-6)
 V10
Insulation resistance
Clearance in air and creepage distances
  EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
  EN 50178
Back-up of real-time clock
Back-up of real-time clock
  
 
  Backup time (hours)
Service life (years)
Retentive memory
Write cycles of the retentive memory
  1000000 (10⁶)
Power supply
Rated operational voltage
UeV24 DC (-15/+20%)
Admissible range
 V DC20.4- 28.8
Residual ripple
 %5
Input current
   
Input current 115/230 V AC
 mANormally 80
Voltage dips
 ms≤10
Heat dissipation
 WNormally 2
Analog outputs
Conversion time, analog/digital
 msDebounce ON: 20; Debounce OFF: every cycle time
Digital inputs 24 V DC
Number
  8
Inputs can be used as analog inputs
  2 (I7, I8)
Status indication
  LCD display (if provided)
Potential isolation
   
From power supply
  No
Between digital inputs
  No
From the outputs
  Yes
Rated operational voltage
UeV DC24
On 0 signal
UeV DC< 5 (I1 - I8)
On 1 signal
UeV DC> 15 (I1 - I6) > 8 (I7, I8)
Rated operational voltage
UeV24 DC (-15/+20%)
Input current on 1 signal
   
I1 to I6
 mA3.3 (at 24 V DC)
I7, I8
 mA2.2 (at 24 V DC)
Delay time from 0 to 1
 ms 
Debounce ON
 ms20
Debounce OFF
 msNormally 0.25 (I1 - I8)
Delay time from 1 to 0
 ms 
Debounce ON
 ms20
Cable length (unscreened)
 m100
Incremental counter
   
Counter frequency
 kHz1
Rapid counter inputs
   
Number
  2 (I1, I2)
Cable length, screened
 m< 20
Counter frequency
 kHz< 1
Pulse shape
  Square
Analog inputs
Quantity
  2 (I7, I8)
Potential isolation
   
From the outputs
  Yes
between the inputs
  No
Input type
  DC voltage
Resolution, analog
 V0.01
Resolution, digital
 V0.01
Resolution
 Bit10 (value 1 - 1023)
Input impedance
 kΩ11.2
Accuracy of actual value
   
Two EASY devices
 %± 3
Within a single device
 %± 2, (I7, I8, I11, I12) ± 0.12 V
Conversion time, analog/digital
 msDebounce ON: 20; Debounce OFF: every cycle time
Input current
 mA< 1
Cable length screened
 m< 3
Relay outputs
Number
  4
Outputs in groups of
  1
Parallel switching of outputs for increased output
  Not permissible
Protection of an output relay
  Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation
   
From power supply
  Yes
From the inputs
  Yes
Potential isolation in groups
  Yes
Safe isolation according to EN 50178
 V AC300
Basic insulation
 V AC600
Lifespan, mechanical
Operationsx 10610
Contacts
   
Conventional thermal current (10 A UL)
 A8
Recommended for load: 12 V AC/DC
 mA> 500
Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
 A16
Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
 A16
Rated impulse withstand voltage Uimpof contact coil
 kV6
Rated operational voltage
UeV AC250
Rated insulation voltage
UiV AC250
Safe isolation to EN 50178 between coil and contact
 V AC300
Safe isolation to EN 50178 between 2 contacts
 V AC300
Making capacity
   
AC-15, 230 V AC, 3 A
Operations 300000
DC-13, 24 V DC, 5 A, 0.1 Hz
Operations 200000
Breaking capacity
   
AC-15, 250 V AC, 3 A (600 Ops./h)
Operations 300000
DC-13 L/R 150 ms 24 V DC, 1 A (500 Ops./h)
Operations 200000
Filament bulb load
   
1000 W at 230/240 V AC
Operations 25000
500 W at 115/120 V AC
Operations 25000
Fluorescent lamp load
   
Fluorescent lamp load 10 x 58 W at 230/240 V AC
   
With upstream electrical device
Operations 25000
Uncompensated
Operations 25000
Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated
Operations 25000
Switching frequency
   
Mechanical operations
 x 10610
Switching frequency
 Hz10
Resistive load/lamp load
 Hz2
Inductive load
 Hz0.5
UL/CSA
   
Uninterrupted current at 240 V AC
 A10
Uninterrupted current at 24 V DC
 A8
AC
   
Control Circuit Rating Codes (utilization category)
  B 300 Light Pilot Duty
Max. rated operational voltage
 V AC300
Max. thermal uninterrupted current cos ϕ = 1 at B 300
 A5
Max. make/break capacity cos ϕ ≠ 1 at B 300
 VA3600/360
DC
   
Control Circuit Rating Codes (utilization category)
  R 300 Light Pilot Duty
Max. rated operational voltage
 V DC300
Max. thermal uninterrupted current at R 300
 A1
Max. make/break capacity at R 300
 VA28/28
Technical data according to ETIM 4.0
Voltage type of supply voltage
  DC
Expandable
  No
With display
  YES
Number of HW-interfaces RS232
  0
Number of HW-interfaces serial TTY
  0
Max. number of integrated digital inputs
  8
Supporting protocol for LON
  No
With time switch
  No
Max. number of integrated analog outputs
  0
Number of HW-interfaces RS485
  0
Max. number of integrated digital outputs
  4
Protection type (IP)
  IP20
Height
 mm90
Width
 mm72
Number of Industrial Ethernet HW interfaces
  0
Number of HW-interfaces RS422
  0
Depth
 mm60
Switching current
 A8
Max. number of integrated analog inputs
  0
With relay output
  YES
Number of HW-interfaces other
  0
Dimensions
4

Opis pochodzi ze strony www.moeller.net .