Moduł ECO ośmiu wejść analogowych (4 mogą być wejściami PT/NI) XNE-8AI-U/I-4PT/NI
Program
I/O modules | |||
Analog input modules | |||
XNE Slice module | |||
Description | 8 Analog input U/I or 4 Analog inputs PT/NI -10/0 to +10 V DC 0/4 to 20 mA Acquisition of normalized signals for temperature measurement Connection of sensor types Pt100, Pt200, Pt500, Pt1000 and Ni100, Ni1000, NI1000TK5000 in 2- or 3-wire circuit | ||
Information relevant for export to North America Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking UL File No.E29184 UL CCNNKCR CSA File No.012528 CSA Class No.3211-03 NA CertificationUL Listed, CSA certified |
Approbationen
|
General | |||
Standards | EN 61000-6-2 EN 61000-6-4 EN 61131-2 | ||
Potential isolation | Yes, through optocoupler | ||
Ambient temperature | °C | 0 - +55 | |
Storage | °C | -25 - +85 | |
Relative humidity | % | 5 - 95 (indoor), level RH-2, non-condensing (at 45 °C storage) | |
Schadgas | ppm | SO2: 10 (rel. Feuchte < 75 %, keine Kondensation) H2S: 1.0 (rel. Feuchte < 75 %, keine Kondensation) | |
Vibrationsfestigkeit, Einsatzbedingungen | gemäß IEC 60068-2-6 | ||
Mechanical shock resistance | g | gemäß IEC 60068-2-27 | |
Continuous shock resistance (IEC/EN 60068-2-29) | According to IEC 60068-2-29 | ||
Drop and topple | According to IEC 60068-2-31, free fall according to IEC 60068-2-32 | ||
Protection type | IP20 | ||
Electromagnetic compatibility (EMC) | |||
ESD | EN 61100-4-2 | ||
Electromagnetic fields | EN 61100-4-2 | ||
Burst | EN 61100-4-4 | ||
Surge | EN 61100-4-5 | ||
HF unsymmetric | EN 61100-4-6 | ||
Emitted interference (radiated, high frequency) | EN 55016-2-3 | ||
Spannungsvariationen | EN 61131-2 | ||
Type test | to EN 61131-2 | ||
Approvals | CE, cUL (ggf. in Bearbeitung) | ||
Other technical data (sheet catalogue) | Technical Data | ||
Terminations | |||
Rated data | nach VDE 0611 Teil 1/8.92/ IEC/EN 60947-7-1 | ||
Connection design in TOP direction | Push-In Federzugklemmen | ||
Stripping length | mm | 8 | |
Clamping range | max. 0.14 - 1.5 mm2 | ||
Connectable conductors | |||
"e" eindrähtig H 07V-U | mm2 | 0.25 - 1.5 | |
"f" feindrähtig H 07V-K | mm2 | 0.25 - 1.5 | |
"f" mit Aderendhülsen ohne Kunstoffkragen nach DIN 46228-1 (Aderendhülsen gasdicht festgedrückt) | mm2 | 0.25 - 1.5 | |
"f" mit Aderendhülsen mit Kunstoffkragen nach DIN 46228-1 (Aderendhülsen gasdicht festgedrückt) | mm2 | 0.25 - 0.75 | |
Gauge pin IEC/EN 60947-1 | A1 | ||
Analog input modules | |||
Messgrössen | Spannung, Strom, Temperatur (PT, NI), Widerstand R | ||
Channels | Number | 8 (U/I), 4 (PT/NI/R) | |
Rated voltage through supply terminal | UL | 24 V DC | |
Rated current consumption from supply terminal | IL | mA | 35 |
Rated current consumption from module bus | IMB | mA | 30 |
Heat dissipation | W | < 1.5 | |
Input current | mA | 0/4 - 20 | |
Maximum input current | mA | 40 (max. Eingangsspannung < 17 V) | |
Input voltage | -10/0 to +10 V DC | ||
Maximum input voltage | V DC | ± 20 | |
Input impedance | < 62 Ω/200 kΩ | ||
Limit frequency (-3 db) | Hz | 1.5 | |
Offset error | % | 0.1 | |
Basic error limit at 23 °C | % | 0.2 | |
Temperature coefficient | 200 ppm/°C vom Endwert | ||
Measured value representation | 16 Bit Signed Integer 12 Bit Full Range linksbündig | ||
Connectable sensors | Platin-Sensoren: PT100, PT500, PT1000 (nach DIN IEC 751) Nickel-Sensoren: Ni100, Ni1000 (nach DIN 43760) | ||
Diagnostics | Yes | ||
Base modules | |||
without C connection | bereits integriert |