Moduł 8 wyjść binarnych systemu XI/ON ECO

  • szt.
  • Rabat: -313,84 zł (40 %)
  • (Rabat brutto: -386,02 zł (40 %))
  • Cena brutto: 579,04 zł / szt. 470,76 zł / szt.
Moduł 8 wyjść binarnych, wersja ECO XNE-8DO-24VDC-0.5A-P
Program
 
  I/O modules
 
  Digital output modules
 
  XNE Slice module
Description
  8 Digital output, 24 V DC/0.5 A
Positive switching
Information relevant for export to North America

Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking

UL File No.E29184

UL CCNNKCR

CSA File No.012528

CSA Class No.3211-03

NA CertificationUL Listed, CSA certified

Approbationen
Product StandardsUL 508; CSA-C22.2 No. 142; IEC/EN 6113-2; CE marking
UL File No.E205091
UL CCNNRAQ, NRAQ7
CSA File No.UL report applies to both US and Canada
CSA Class No.2252-01, 2252-81
NA CertificationUL Recognized, certified by UL for use in Canada
Specially designed for NANo
Current Limiting CBNo
Degree of ProtectionIEC: IP20, UL/CSA Type: -
 
General
Standards
  EN 61000-6-2
EN 61000-6-4
EN 61131-2
Potential isolation
  Yes, through optocoupler
Ambient temperature
 °C0 - +55
Storage
 °C-25 - +85
Relative humidity
 %5 - 95 (indoor), level RH-2, non-condensing (at 45 °C storage)
Schadgas
 ppmSO2: 10 (rel. Feuchte < 75 %, keine Kondensation)
H2S: 1.0 (rel. Feuchte < 75 %, keine Kondensation)
Vibrationsfestigkeit, Einsatzbedingungen
  gemäß IEC 60068-2-6
Mechanical shock resistance
 ggemäß IEC 60068-2-27
Continuous shock resistance (IEC/EN 60068-2-29)
  According to IEC 60068-2-29
Drop and topple
  According to IEC 60068-2-31, free fall according to IEC 60068-2-32
Protection type
  IP20
Electromagnetic compatibility (EMC)
   
ESD
  EN 61100-4-2
Electromagnetic fields
  EN 61100-4-2
Burst
  EN 61100-4-4
Surge
  EN 61100-4-5
HF unsymmetric
  EN 61100-4-6
Emitted interference (radiated, high frequency)
  EN 55016-2-3
Spannungsvariationen
  EN 61131-2
Type test
  to EN 61131-2
Approvals
  CE, cUL (ggf. in Bearbeitung)
Other technical data (sheet catalogue)
  Technical Data
Terminations
Rated data
  nach VDE 0611 Teil 1/8.92/

IEC/EN 60947-7-1
Connection design in TOP direction
  Push-In Federzugklemmen
Stripping length
 mm8
Clamping range
  max. 0.14 - 1.5 mm2
Connectable conductors
   
"e" eindrähtig H 07V-U
 mm20.25 - 1.5
"f" feindrähtig H 07V-K
 mm20.25 - 1.5
"f" mit Aderendhülsen ohne Kunstoffkragen nach DIN 46228-1 (Aderendhülsen gasdicht festgedrückt)
 mm20.25 - 1.5
"f" mit Aderendhülsen mit Kunstoffkragen nach DIN 46228-1 (Aderendhülsen gasdicht festgedrückt)
 mm20.25 - 0.75
Gauge pin IEC/EN 60947-1
  A1
Digital output modules
Channels
 Number8
Rated voltage through supply terminal
UL 24 V DC
Rated current consumption from the supply terminal (at load current = 0 mA)
ILmA3
Rated current consumption from module bus
IMBmA15
Power loss
 WNormally 1.5
Output voltage
   
High level
UH⁄UA > UL- 1 V DC
Output current
 A 
High level (rated value)
IH 0.5 A
High level (permissible range)
IHA< 1.0
Delay on signal change and resistive load
   
from Low to High level
 µs300
From High to Low signal
 µs300
Utilization factor
%g100
Can be connected
  Resistive loads
Inductive loads
Lamp loads
Resistive load
 48
Inductive load
 hgemäß DC13 nach IEC 60947-5-1
Lamp load
RLLW6
Switching frequency
   
With resistive load
fHz100
bei induktiver Last
  gemäß DC13 nach IEC 60947-5-1
with lamp load
 Hz10
Ausgang nach EN 61131-2
  short-circuit proof
Reset after short-circuit rectified
Ii Automatic
Notes

The supply terminal (UL) provides power for the module electronics and for the consumers at the outputs. The total current required for each module consists of the sum of all partial currents.

Part of the XI/ON module’s electronics is supplied with module bus voltage (5 V DC), the other part through the supply terminal (UL).

To increase the maximum output current to up to 1 A, two outputs can be connected in parallel.

Dimensions

Opis pochodzi ze strony www.moeller.net .