Zabezpieczenie termistorowe;siln.przek.przeciąż. EMT6-DB

  • pcs.
  • Gross price: 1,386.21 zł 1,127.00 zł

Zabezpieczenie termistorowe;siln.przek.przeciąż. EMT6-DB

Program
Product range
    EMT6 thermistor overload relay for machine protection
Function
    Selector switch with/without automatic reset
For manual or remote resetting
Test button
Mains and fault LED display
Rated operational current
     
AC-15
     
240 V
Ie A 3
AC--14
     
400 V
Ie A 3
conventional thermal current
Ith A 6
Rated control voltage
Us V 24 - 240 V 50/60 Hz,
24 - 240 V DC
Notes

 

II (2) G

II (2) GD only for EMT6-K

 

Observe the manual AWB2327-1446 →#264853

Can be snap fitted on a top-hat rail to IEC/EN 60715.

Spacing of devices 3 mm.

 

1) EMT6, EMT6(230V), EMT6-DB and EMT6-DB(230V):an additional short-circuit protection in the sensor circuit with current monitor is to be provided.

Information relevant for export to North America

Product StandardsIEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking

UL File No.E29184

UL CCNNKCR

CSA File No.012528

CSA Class No.3211-03

NA CertificationUL Listed, CSA certified

Approbationen
Product Standards UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No. E29184
UL CCN NKCR
CSA File No. 12528
CSA Class No. 3211-03
NA Certification UL Listed, CSA certified
Specially designed for NA No
Max. Voltage Rating 600 V AC
Degree of Protection IEC: IP20, UL/CSA Type: -
 
General
Standards
    IEC/EN 60947, VDE 0660, EN 55011
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
  °C  
Open
  °C -25- 60
Enclosed
  °C -25- 45
Storage
  °C -45- 60
Mounting position
    As required
Weight
  kg 0.15
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
  g 10
Protection type
    IP20
Protection against direct contact when actuated from front (EN 90274)
    Finger- and back-of-hand proof
Safe isolation to VDE 0106 Part 101 and Part 101/A1
     
between the contacts
  V AC 250
between contacts and power supply
  V AC 250
Auxiliary and control circuits
Rated impulse withstand voltage
Uimp V AC 6000
Overvoltage category/pollution degree
    III/3
Terminal capacities Auxiliary and control circuits
     
Solid
  mm2 1 x 2.5
2 x (0.5 - 1.5)
Flexible with ferrule
  mm2 1 x 2.5
2 x (0.5 - 1.5)
Solid or stranded
  AWG 20 - 14
Terminal screw
    M3.5
Tightening torque
  Nm 1.2
Tools
     
Pozidriv screwdriver
  Size 2
Standard screwdriver
  mm 1 x 6
Auxiliary power circuit
Rated insulation voltage
Ui V 400
Rated operational current
Ie A  
AC--14
     
Make contact
     
415 V
Ie A 3
Break contact
     
415 V
Ie A 3
AC-15
     
Make contact
     
240 V
Ie A 3
415 V
Ie A 1
Break contact
     
240 V
Ie A 3
415 V
Ie A 1
Max. short-circuit protective device
     
Fuse
gG/gL A 6
Control circuit
Rated insulation voltage
Ui V 240
Rated operational voltage
Ue V 240
Pick-up and drop-out values
  x Ue 0.85- 1.1
Power consumption
     
AC
  VA 3.5
DC
  W 2
Trip at approx.
  3600
Recovery at approx.
  1600
Notes
Notes EMT6(-DB)230V: Ue= 230 V
Technical data according to ETIM 4.0
Width
  mm 23
Height
  mm 83
Depth
  mm 103
With detachable clamps
    No
Error registration possible
    No
Number of measuring circuits
    1
External reset possible
    YES
Type of electric connection
    Screw connection
Rated control supply voltage Us at AC 50HZ
  V 240
Rated control supply voltage Us at AC 60HZ
  V 240
Rated control supply voltage Us at DC
  V 240
Voltage type for actuation
    AC/DC
Number of contacts as normally closed contact
    1
Number of contacts as normally open contact
    1
Number of contacts as change-over contact
    0
Dimensions

Opis pochodzi ze strony www.moeller.net .